Hybrid Inverter SL5-12KRH-W
Parameter List
MODEL | SL5KRH-W | SL6KRH-W | SL8KRH-W | SL10KRH-W | SL12KRH-W |
PV (DC) | |||||
---|---|---|---|---|---|
Recommended Max. PV Input Power | 7500 Wp | 9000 Wp | 10000 Wp | 15000 Wp | 18000 Wp |
Max. Input Voltage* | 1000 V | ||||
Start-up Voltage | 135 V | ||||
Rated Input Voltage | 600 V | ||||
MPPT Input Voltage Range* | 135-900 V | ||||
MPPT Max. Input Current | 16 A / 16 A | 16 A / 32 A | |||
MPPT Short-circuit Current | 20 A / 20 A | 20 A / 40 A | |||
No. of MPPT | 2 | ||||
No. of Strings per MPPT | 1 / 1 | 1 / 2 | |||
Grid (AC) | |||||
Max. Input Apparent Power** | 10000 VA | 12000 Wp | 16000 VA | 20000 Wp | 24000 Wp |
Rated Output Power | 5000 W | 6000 W | 8000 W | 10000 W | 12000 W |
Max. Output Apparent Power | 5500 VA | 6600 VA | 8800 VA | 11000 VA | 13200 VA |
Rated AC Voltage | 3L/N/PE, 220/380 V, 230/400 V, 240/415 V | ||||
Input/Output Voltage Range | 180-300 V / 200-253 V | ||||
Rated Output Voltage Frequency | 50/60 Hz | ||||
Input/Output Voltage Frequency Range | (45-55)/(55-65) Hz | ||||
Rated Output Current | 7.2 A | 8.7 A | 11.6 A | 14.5 A | 17.4 A |
Max. Input/Output Current | 15.2 A / 9.8 A | 18.2 A / 11.8 A | 24.2 A / 15.8 A | 30.3 A / 19.7 A | 36.4 A / 23.6 A |
Power Factor (Rated) | >0.99 | ||||
Adjustable Power Factor Range | 0.8 leading ... 0.8 lagging | ||||
Total Harmonic Distortion | <3% (Rated Power) | ||||
Grid Connection Mode | 3L/N/PE | ||||
AC Load Output (Off-grid) | |||||
Rated Output Power | 5000 W | 6000 W | 8000 W | 10000 W | 12000 W |
Max. Output Apparent Power | 5500 VA | 6600 VA | 8800 VA | 11000 VA | 13200 VA |
Rated Output Voltage | 3L/N/PE, 220/380 V, 230/400 V, 240/415 V | ||||
Output Voltage Range | 200-240 V | ||||
Rated Output Frequency | 50/60 Hz | ||||
Rated Output Current | 7.2 A | 8.7 A | 11.6 A | 14.5 A | 17.4 A |
Max. Output Current | 9.8 A | 11.8 A | 15.8 A | 19.7 A | 23.6 A |
Total Harmonic Distortion | <3% (R Load) | ||||
On-grid/Off-grid Switching Time | <10 ms | ||||
Battery (DC) | |||||
Rated Output Power | 5000 W | 6000 W | 8000 W | 10000 W | 12000 W |
Max.Charge/Discharge Power | 12500 W / 5500 W | 12500 W / 6600 W | 12500 W / 8800 W | 12500 W / 11000 W | 12500 W / 13200 W |
Battery Voltage Range | 135-800 V | ||||
Max. Charge/Discharge Current | 25A / 25 A | ||||
Communication Port | CAN/RS485 | ||||
Efficiency | |||||
Max. efficiency | 97.6% | ||||
Max. MPPT Efficiency | 99.9% | ||||
Max. European Efficiency | 97.0% |
* Max. DC input voltage is 1000V without battery, 850V with battery. If the voltage is greater than the maximum, the inverter is in standby state.
** Max. grid input power refers to the max. power drawn from the grid, including the supply of off-grid load and battery charging.
Protection | |
Integrated Protection | Anti-flow Protection, DC Reverse Protection, DC Circuit Breaker, Insulation Resistor Detection, Leakage Current Monitoring, Output Shorted Protection, Output Over Current Protection, Grid Monitoring, Anti-islanding Protection, Residual Current Monitoring, Reverse Polarity Protection, Off-grid Overload Protection. |
Surge Protection | DC Type II, AC Type II |
Display and Communication | |
---|---|
Display | LED+APP |
Communication | Yes: RS485 / USB , Optional: 4G / WiFi |
General ` | |
Dimensions (W×H×D) | 516×442×222 mm |
Weight | 24 kg |
Operating Temperature Range | -30~60 ℃ |
Noise | <35 dB |
Cooling | Smart Cooling |
Installation Style | Wall-mounted |
Protection Rating | IP66 |
Warranty | 10 Years |
Standards Compliance | |
---|---|
Grid Connection | EN 50549-1, CEI 0-21, AS 4777.2, G98/G99, EN 50438, VDE 4105, VDE 0126 |
Safety Regulation | IEC/EN 62109-1/2 |
Others | IEC/EN 61000-6-1/2/3/4 |