PCS SL125KRP-W
Parameter List
Model | SL125KRP-W |
DC side (Battery) | |
DC voltage range | 600V-1000V |
Max. Charge/Discharge current | 160 A |
AC side (Grid) | |
Nominal AC output power | 125 kVA |
Max. AC output power | 137.5 kVA |
Nominal AC voltage | 400 V |
Nominal grid frequency | 50/60Hz |
Grid frequency range | 45~55Hz/55~65Hz |
AC connection | 3L/N |
Nominal AC output current | 181 A |
Max. AC output current | 199 A |
Power factor at nominal power /Adjustable power factor | >0.99/-1~1 |
Max.THD of current | <3% (at nominal power) |
Efficiency | |
Max. efficiency | 98.5% |
Protection | |
DC input protection | Yes |
Protection level/overvoltage level | I/ll |
Surge protection | DC Type ll, AC Type ll |
Display and Communication | |
Display | LED |
Communication | CAN/RS485/DI/DO/Ethernet |
General data | |
Dimensions (W×H×D) | 700×280×850 mm |
Weight | 80 kg |
Operating ambient temperature range | -20~60℃ |
Allowable relative humidity range | 0~100%(non-condensing) |
Max. operating altitude | 3000 m |
Noise | <80dB |
Cooling method | Intelligent air cooling |
Ingress Protection Rating | IP66 |
Warranty | 10 years |
DC connection type | Plug and unplug terminal |
AC connection type | Plug and unplug terminal |
Standards Compliance | |
Grid Connection | GB/T 34120/34133, EN 50549-1, CEl 0-21, VDE-AR-N 4105, NTS Type A&B, RD 1699/661/413/647/244/2019, UNE 206006/206007/217001/217002 |
Safety Regulation | EN/IEC 62109-1/2 |
Others | EN/IEC 61000-6-1/2/3/4 |